A boiler should send out steam and keep its water. Carryover is when boiler water, with everything dissolved in it, leaves with the steam instead. It wets the steam, contaminates the process, deposits solids in valves and superheaters, and can hammer the mains.

ByShikhar Singh·Steam Consultant & IT Consultant·Published

You'll learn

  • Distinguish priming, foaming and carryover
  • Know the causes of each
  • Recognize the symptoms downstream
  • Prevent and correct carryover

Before this: TDS control and blowdown, Wet, dry and superheated steam

BeginnerThe idea in plain words, and where you meet it. No maths.

Water where steam should be

  • Priming: slugs of boiler water thrown into the steam outlet, usually by a sudden surge in steam demand or a water level that is too high.
  • Foaming: a stable froth on the water surface, caused by dissolved solids, alkalinity, oil or organic contamination, that fills the steam space and is drawn out with the steam.
  • Carryover: the general term for any boiler water leaving with the steam, from fine mist to slugs.

Carried-over water is not just water: it is concentrated boiler water, carrying dissolved solids and treatment chemicals into the steam system.

IntermediateThe formula, its units, and a worked example on real plant numbers.

Causes

What causes carryover
CauseWhy
High boiler water TDS or alkalinityMakes the water foam; the froth fills the steam space
Oil or organic contaminationOften from condensate; a powerful foaming agent
Water level too highLess steam space for separation; spray reaches the outlet
Sudden large steam demandPressure drops, water swells and surges toward the outlet
Running far above ratingSteam velocity through the water surface is too high for separation
Low steam pressure for the loadSteam occupies more volume and rushes out faster

Several of these act together. A boiler running at low pressure, high load and high TDS, with a sudden process start-up, is the classic case.

ExpertThe fine print: where the simple model breaks, and what it costs.

Symptoms and prevention

  • Gauge glass level unstable or jumping.
  • Water hammer in the steam mains, especially after a load surge.
  • Steam traps and control valves fouled with deposits; process heaters losing output.
  • High conductivity in condensate that has not been contaminated by the process — the dissolved solids came from the boiler.
  • Superheater and turbine deposits, where fitted: the most expensive consequence.
  • Hold TDS and alkalinity within limits with correct blowdown.
  • Keep the water level at its normal working level, not above.
  • Keep oil and process contamination out: monitor condensate and dump it when contaminated.
  • Avoid sudden large steam demands; open process valves gradually and keep the boiler within its rating.
  • Do not run at much lower pressure than designed: steam volume and outlet velocity rise.
  • Fit a steam separator after the boiler where clean, dry steam is critical.

Key takeaways

  • Priming throws slugs of water; foaming fills the steam space with froth; both cause carryover.
  • Causes: high TDS or alkalinity, contamination, high level, sudden demand, overload, low pressure.
  • Carryover brings boiler solids into valves, traps, superheaters and the process.
  • Prevent with blowdown, level control, clean condensate, gradual loading and a separator.

Check your understanding

Questions run from beginner to expert. Try each before opening the answer.

  1. Beginner

    Q1. What is carryover?

    1. A.Steam leaking from a valve
    2. B.Boiler water leaving with the steam
    3. C.Fuel left in the ash
    4. D.Ash carried in flue gas
    Show answer

    B. Water and its solids go out with the steam.

  2. Intermediate

    Q2. Which commonly causes foaming?

    1. A.Low TDS
    2. B.Oil contamination in the boiler water
    3. C.High stack temperature
    4. D.Dry fuel
    Show answer

    B. Oil and organics are strong foaming agents.

  3. Intermediate

    Q3. Why does a sudden large steam demand cause priming?

    1. A.It cools the boiler
    2. B.Pressure drops, water swells and surges to the outlet
    3. C.It adds TDS
    4. D.It lowers the level
    Show answer

    B. Swell pushes water into the steam outlet.

  4. Expert

    Q4. Condensate conductivity is high but the process is clean. Likely cause?

    1. A.Carryover of boiler water
    2. B.Too much excess air
    3. C.Cold feed
    4. D.Clean steam
    Show answer

    A. The dissolved solids came from the boiler with the steam.

Frequently asked

What is the difference between priming and foaming?
Priming is boiler water thrown out with the steam in slugs, usually by a load surge or high level. Foaming is froth on the water surface, from high TDS, alkalinity or contamination, drawn out with the steam.
How do you prevent boiler carryover?
Keep TDS and alkalinity within limits, keep the water level normal, keep oil out of the condensate, avoid sudden large loads and overloading, and fit a steam separator where needed.

Training a boiler team?

These lessons follow the order we train operators in. We also run on-site operator and maintenance training, built around your own plant.

Boiler operator training →