Module 01 · Steam Properties5 min read

Wet, Dry and Superheated Steam, and the Dryness Fraction

Steam comes in three conditions. Wet steam carries droplets of water, dry saturated steam carries none, and superheated steam has been heated beyond its boiling point. Which one a plant gets, and how wet it is, changes how much heat each kilogram delivers.

ByShikhar Singh·Steam Consultant & IT Consultant·Published

You'll learn

  • Tell wet, dry saturated and superheated steam apart
  • Use the dryness fraction to find the enthalpy of wet steam
  • Explain why heating processes want dry saturated steam, not superheated
  • Understand how dryness is measured

Before this: Saturation pressure and temperature, Enthalpy

BeginnerThe idea in plain words, and where you meet it. No maths.

Three conditions of steam

  • Wet steam: saturated steam with fine water droplets carried along in it. Most steam leaving a shell boiler is slightly wet, and it gets wetter in an uninsulated pipe as some of it condenses.
  • Dry saturated steam: steam at its saturation temperature with no liquid in it. The ideal for process heating.
  • Superheated steam: steam heated above its saturation temperature after all the water has boiled off. Used for turbines and some special processes.

Wet and dry saturated steam are at the same temperature for a given pressure; you cannot tell them apart with a thermometer. Superheated steam is hotter than its saturation temperature, and a thermometer shows it.

IntermediateThe formula, its units, and a worked example on real plant numbers.

The dryness fraction

The dryness fraction, x, is the share of a wet steam mixture that is actually steam. Steam with x = 0.95 is 95% steam and 5% water by mass. Only the steam part has picked up latent heat, so the enthalpy is:

Enthalpy of wet steam
h=hf+xhfg
Symbols in the formula
SymbolMeaningUnit
xDryness fraction, 0 for water to 1 for dry steam—
hfEnthalpy of saturated waterkJ/kg
hfgLatent heatkJ/kg
Worked example
Steam 95% dry at 10 kg/cm²(g)
Given
  • hf = 778.0 and hfg = 2,002.1 kJ/kg at 10 kg/cm²(g).
  1. Enthalpy of the mixture:
    h=778.0+0.95×2,002.1=2,680.0 kJ/kg
  2. Latent heat it can deliver on condensing: 1,902.0 kJ/kg, against 2,002.1 for dry steam.
Answer: Each kilogram delivers 5% less latent heat, so the process needs 5.3% more steam for the same load — and the water carried along also wets heat transfer surfaces and wears valves.

For superheated steam, the measure is the degree of superheat: how far above saturation it is. Steam at 10 kg/cm²(g) and 250 °C has 67 °C of superheat and an enthalpy of 2,940.2 kJ/kg.

ExpertThe fine print: where the simple model breaks, and what it costs.

Why process heating wants dry saturated steam

It sounds as if superheated steam should heat better: it carries more heat per kilogram. But the extra 160 kJ/kg of superheat is sensible heat in a gas, and a gas gives up heat poorly. Until superheated steam has cooled to its saturation temperature it behaves like hot air against a heat transfer surface, with a heat transfer coefficient many times lower than condensing steam. The first part of the exchanger does little work.

Superheat also breaks the link between pressure and temperature, so a process can no longer be controlled by pressure alone. That is why superheated steam from a turbine exhaust or a power boiler is usually passed through a desuperheater, which sprays in water to bring it back to saturation, before it is used for heating.

Wet steam comes from three places: priming and carryover in the boiler, condensation in poorly insulated or poorly drained mains, and droplets that a reducing valve does not dry out completely. A separator before critical users removes the water mechanically.

Key takeaways

  • Wet and dry saturated steam share a temperature; superheated steam is hotter than saturation.
  • Enthalpy of wet steam: h=hf+xhfg. Wet steam delivers proportionally less latent heat.
  • Process heating wants dry saturated steam; superheat transfers heat poorly until it is removed.
  • Dryness is measured by throttling a sample and reading its temperature.

Check your understanding

Questions run from beginner to expert. Try each before opening the answer.

  1. Beginner

    Q1. Which two kinds of steam have the same temperature at a given pressure?

    1. A.Wet and superheated
    2. B.Wet and dry saturated
    3. C.Dry saturated and superheated
    4. D.All three
    Show answer

    B. Both are at saturation temperature; only superheated steam is hotter.

  2. Intermediate

    Q2. Steam has a dryness fraction of 0.9. What share of its mass is water droplets?

    1. A.0.9%
    2. B.9%
    3. C.10%
    4. D.90%
    Show answer

    C. x = 0.9 means 90% steam, 10% water.

  3. Intermediate

    Q3. hf = 700 and hfg = 2,000 kJ/kg. What is h for x = 0.95?

    1. A.2,700 kJ/kg
    2. B.2,600 kJ/kg
    3. C.2,565 kJ/kg
    4. D.1,900 kJ/kg
    Show answer

    B. 700 + 0.95 × 2,000 = 2,600 kJ/kg.

  4. Expert

    Q4. Why does superheated steam make a poor heating medium in a process exchanger?

    1. A.It is too cold
    2. B.Until it desuperheats it gives up heat like a gas, with a low transfer coefficient
    3. C.It contains water
    4. D.It cannot be condensed
    Show answer

    B. Condensing steam transfers heat far better than superheated vapor cooling as a gas.

Frequently asked

What is the dryness fraction of steam?
The mass fraction of a wet steam mixture that is vapor. x = 1 is dry saturated steam, x = 0.95 means 5% of the mass is water droplets.
What is the difference between saturated and superheated steam?
Saturated steam is at the boiling temperature for its pressure; superheated steam has been heated above it. Superheated steam has a temperature independent of its pressure.
Is superheated steam better for process heating?
Usually not. Its superheat transfers poorly, like hot gas, and it breaks pressure-based temperature control. Process heating uses dry saturated steam; superheat is for turbines.

Related equipment

Training a boiler team?

These lessons follow the order we train operators in. We also run on-site operator and maintenance training, built around your own plant.

Boiler operator training →