Blowdown Heat Recovery: Flash Vessel and Heat Exchanger

Continuous blowdown leaves the boiler as water at full saturation temperature. Sent straight to drain, all that heat is lost. A flash vessel and a heat exchanger recover most of it, and it is one of the simplest heat recovery projects in a boiler house.

ByShikhar Singh·Steam Consultant & IT Consultant·Published

You'll learn

  • Calculate the heat leaving in blowdown
  • Explain flash recovery to the deaerator
  • Explain heat exchange to the make-up water
  • Estimate the fuel saved

Before this: TDS control and blowdown, Flash vessels

BeginnerThe idea in plain words, and where you meet it. No maths.

Hot water down the drain

At 10.54 kg/cm²(g), boiler water is at 185.5 °C and carries 787.4 kJ/kg. Blowdown leaves at that enthalpy. It was fed in as cold make-up, so every kilogram blown down takes the difference with it — along with water that was paid for, softened and dosed.

Recovery works in two stages. First, the blowdown is let down into a flash vessel at low pressure, where part of it flashes to clean steam that goes to the deaerator or feed tank. Second, the remaining hot water passes through a heat exchanger that warms incoming make-up before it goes to drain.

IntermediateThe formula, its units, and a worked example on real plant numbers.

A worked example

Worked example
Blowdown recovery on a 5 TPH boiler
Given
  • 5,000 kg/h of steam at 10.54 kg/cm²(g); continuous blowdown 4% (200 kg/h); flash vessel at 0.5 kg/cm²(g); make-up at 30 °C; exchanger cools the drain to 40 °C.
  1. Heat leaving in blowdown, against make-up: 200 × (787.4 − 125.8) = 1,32,308 kJ/h.
  2. Flash: 14.4% flashes, 28.8 kg/h of steam to the deaerator, recovering 73,818 kJ/h.
  3. Exchanger: 171.2 kg/h cooled from 111.4 to 40 °C recovers 51,333 kJ/h into the make-up.
  4. Recovered: 1,25,151 kJ/h, or 95% of the blowdown heat.
Answer: About 9.1 kg/h of coal, or 66 t a year over 7,200 hours.
ExpertThe fine print: where the simple model breaks, and what it costs.

Design points

  • Recovery suits continuous blowdown, which is steady. Intermittent bottom blowdown carries sludge and is better sent to a blowdown vessel.
  • The flash vessel needs a float trap to drain the liquid and a safety valve; the flash steam line goes to a point that can always use it.
  • Blowdown carries dissolved solids and some suspended matter: choose an exchanger that can be cleaned, and keep the hot side free-draining.
  • Recovery is worth most where blowdown is high — hard or high-TDS make-up, little condensate return. Cutting the blowdown rate itself, through better feedwater, comes first.

Key takeaways

  • Blowdown leaves at saturation temperature; all of that heat above make-up is lost if drained.
  • A flash vessel recovers clean low-pressure steam; an exchanger recovers heat from the rest.
  • Together they recover most of the blowdown heat.
  • Reduce the blowdown rate first, then recover what remains.

Check your understanding

Questions run from beginner to expert. Try each before opening the answer.

  1. Beginner

    Q1. At what temperature does continuous blowdown leave the boiler?

    1. A.Feedwater temperature
    2. B.Boiler saturation temperature
    3. C.100 °C
    4. D.Ambient
    Show answer

    B. It is boiler water.

  2. Intermediate

    Q2. Where does recovered flash steam from blowdown usually go?

    1. A.The process
    2. B.The deaerator or feed tank
    3. C.The stack
    4. D.The drain
    Show answer

    B. It is low-pressure steam, ideal for feedwater heating.

  3. Intermediate

    Q3. What heats the make-up water in the second stage?

    1. A.Flash steam
    2. B.The residual hot blowdown, through a heat exchanger
    3. C.The economizer
    4. D.Electricity
    Show answer

    B. The liquid left after flashing.

  4. Expert

    Q4. What should be done before investing in blowdown recovery?

    1. A.Raise the TDS limit blindly
    2. B.Control blowdown on conductivity to the minimum needed
    3. C.Stop blowdown
    4. D.Raise pressure
    Show answer

    B. Recover only what is genuinely required.

Frequently asked

How much heat can blowdown heat recovery save?
Most of the heat in continuous blowdown. A flash vessel returns low-pressure steam to the deaerator and a heat exchanger warms make-up water with the remaining hot water.
What is a blowdown flash vessel?
A vessel at low pressure into which continuous blowdown is released. Part of it flashes to steam, which is reused; the remaining water is drained through a trap, often via a heat exchanger.

Training a boiler team?

These lessons follow the order we train operators in. We also run on-site operator and maintenance training, built around your own plant.

Boiler operator training →

Sources

  • IAPWS-IF97, computed by GyanTosh’s steam engine — Saturation enthalpies and flash fraction.
  • Bureau of Energy Efficiency, Guide Book 2: Energy Efficiency in Thermal Utilities — Blowdown heat recovery.

About the author

Shikhar SinghSteam Consultant & IT Consultant

Shikhar Singh is a Steam Consultant and IT Consultant at GyanTosh Fabricators Pvt. Ltd., where he works on steam system sizing, condensate recovery and the engineering content published on this site.

Full profile and background →