The Heat Exchanger Equation: U-value, LMTD and Fouling
Every heat exchanger, from a boiler economizer to a process heater, follows one equation: heat transferred equals an overall coefficient, times area, times a mean temperature difference. Knowing how each term behaves explains how exchangers are sized and why they lose output as they foul.
You'll learn
- Use Q = U A LMTD
- Calculate a log mean temperature difference
- Understand what the overall U-value includes
- Allow for fouling
Before this: Conduction, convection and radiation, Sensible heat
Three things decide how much heat moves
- How easily heat crosses the wall between the fluids — the overall coefficient, U.
- How much wall there is — the area, A.
- How big the temperature difference is between the two fluids — the driving force.
Double any one of them and, other things equal, the heat transferred doubles. A dirty exchanger loses U; a small one lacks A; one fed with steam at too low a pressure lacks temperature difference.
Q = U A LMTD
| Symbol | Meaning | Unit |
|---|---|---|
| , | Temperature differences between the fluids at the two ends | K |
- 5,000 kg/h of water heated from 30 to 80 °C by steam at 4 kg/cm²(g) (151.4 °C).
- Overall U assumed at 1,500 W/(m²·K) for illustration.
- End differences: 121.4 K and 71.4 K.
- LMTD:
- Heat duty: 290 kW.
- Area:
What U contains, and fouling
| Symbol | Meaning | Unit |
|---|---|---|
| , | Film coefficients on each side | W/(m²·K) |
| Wall resistance | m²·K/W | |
| Fouling resistance allowance | m²·K/W |
Fouling — scale, sludge, product deposits, soot — adds resistance over time. Designers add a fouling allowance so that the exchanger still meets duty when dirty. Adding 0.0002 m²·K/W to the example drops U from 1,500 to 1,154 and raises the required area from 2.1 to 2.7 m².
Arithmetic mean temperature difference overstates the driving force whenever the end differences are very unequal; LMTD is the correct mean for exchangers with one side at constant temperature, as condensing steam is. For other flow arrangements, a correction factor is applied to the counterflow LMTD.
Key takeaways
- Q = U × A × LMTD.
- LMTD = (ΔT₁ − ΔT₂) / ln(ΔT₁/ΔT₂).
- 1/U is the sum of the film, wall and fouling resistances.
- Fouling allowances add area; cleaning restores U.