Module 04 · Fuels4 min read

Oil and Gas Boiler Fuels: Furnace Oil, LDO, HSD, LPG and PNG

Oil and gas are the easy fuels to burn: no ash to handle, quick to start and stop, simple to control. What separates them is cost, availability and handling. Furnace oil must be heated before it can be pumped and burned; gas needs nothing but a pipe and careful safety.

ByShikhar Singh·Steam Consultant & IT Consultant·Published

You'll learn

  • Know the common liquid and gaseous boiler fuels in India
  • Compare their heat values and units
  • Understand why furnace oil is preheated
  • Know the safety and emission points of each

Before this: GCV vs NCV

BeginnerThe idea in plain words, and where you meet it. No maths.

The fuels

Indicative heat values used by GyanTosh’s steam cost tool
FuelIndicative GCVCharacter
Furnace oil (FO)9,800 kcal/kgHeavy, viscous residual oil; must be heated to pump and atomize
Light diesel oil (LDO)10,100 kcal/kgLighter blend; pumps cold, used in smaller boilers
High-speed diesel (HSD)about LDO’sTransport fuel; clean but expensive for boilers
LPGhigh, per kgStored as liquid under pressure; vaporized for burning
Natural gas (PNG)9,000 kcal/SCMPiped; cleanest to burn; no storage on site

Typical figures marked low confidence in the tool. Supplier certificates and gas distributors give actual values.

Notice the units. Liquid fuels are bought and measured by kilogram or liter; piped gas by standard cubic meter (SCM). Comparing them means converting each to price per unit of heat.

IntermediateThe formula, its units, and a worked example on real plant numbers.

Handling each fuel

  • Furnace oil is too viscous to pump or atomize cold. Storage tanks are heated (often with steam coils) and a line heater raises it to the temperature the burner needs for fine atomization. Too cold and it atomizes poorly and smokes; too hot and it can carbonize in the heater.
  • LDO and HSD pump cold and need only filtering. They suit small boilers and standby firing.
  • LPG is stored under pressure as a liquid and vaporized; large installations use vaporizers. It is heavier than air, so a leak pools at ground level and in pits.
  • Natural gas arrives by pipeline through a pressure-regulating station. It is lighter than air and disperses upward, but a leak in an enclosed space is still explosive.

All of them need the same discipline at the burner: proven air flow before ignition, a purge of the furnace before every light-up, a flame detector that shuts the fuel off if the flame fails. The burners and flame safety lesson covers that in detail.

ExpertThe fine print: where the simple model breaks, and what it costs.

Sulfur, dew point and choosing a fuel

Furnace oil carries significant sulfur. Burnt, it forms SO₂ and a little SO₃, which raises the flue gas acid dew point. That sets a minimum stack temperature and a minimum economizer feedwater temperature, so an oil-fired boiler cannot recover as much flue gas heat as a gas-fired one. Natural gas is essentially sulfur-free, which is why gas boilers can carry deeper heat recovery, including condensing economizers.

Oil and gas have high hydrogen content, so their GCV and NCV differ more than coal’s in percentage terms: natural gas’s NCV is about a tenth below its GCV. Burner and boiler efficiency claims for gas are therefore especially sensitive to which basis is quoted.

Key takeaways

  • FO must be heated to pump and atomize; LDO and HSD pump cold; LPG is stored under pressure; PNG arrives by pipe.
  • Compare fuels by price per unit of heat, converting kg, liters and SCM.
  • Sulfur in oil raises the acid dew point and limits heat recovery; gas is nearly sulfur-free.
  • LPG is heavier than air and pools; natural gas rises. Both demand purge and flame safety.

Check your understanding

Questions run from beginner to expert. Try each before opening the answer.

  1. Beginner

    Q1. Which fuel must be heated before it can be pumped and atomized?

    1. A.Natural gas
    2. B.LDO
    3. C.Furnace oil
    4. D.LPG
    Show answer

    C. Furnace oil is too viscous when cold.

  2. Intermediate

    Q2. Where does leaked LPG collect?

    1. A.At the roof
    2. B.At ground level and in pits
    3. C.It disperses instantly
    4. D.Inside the boiler
    Show answer

    B. LPG vapor is heavier than air.

  3. Intermediate

    Q3. Natural gas is usually billed in:

    1. A.kg
    2. B.Liters
    3. C.SCM
    4. D.Tonnes
    Show answer

    C. Standard cubic meters of gas.

  4. Expert

    Q4. Why can a gas-fired boiler recover more flue gas heat than an oil-fired one?

    1. A.Gas burns hotter
    2. B.Gas is nearly sulfur-free, so its acid dew point is low
    3. C.Gas has more ash
    4. D.Oil boilers have no economizer
    Show answer

    B. Low sulfur allows colder flue gas and metal without acid corrosion.

Frequently asked

Why is furnace oil heated before burning?
It is too viscous to pump or atomize when cold. Heating lowers its viscosity so the burner can break it into a fine spray that burns completely.
Which is cheaper for a boiler, oil or gas?
It depends on local prices. Convert each fuel’s price to cost per unit of heat delivered, using its GCV and the boiler’s efficiency on it; GyanTosh’s steam cost calculator does this.

Training a boiler team?

These lessons follow the order we train operators in. We also run on-site operator and maintenance training, built around your own plant.

Boiler operator training →

Sources

  • GyanTosh Steam Cost Calculator, fuel data — Indicative GCVs for furnace oil, LDO and natural gas, marked low confidence.
  • Bureau of Energy Efficiency, Guide Book 2: Energy Efficiency in Thermal Utilities, chapter on fuels and combustion — Properties and handling of liquid and gaseous fuels.