Module 12 · Efficiency and Audits4 min read

Boiler Efficiency Testing: Direct and Indirect Methods

There are two ways to measure a boiler’s efficiency. The direct method divides heat in the steam by heat in the fuel. The indirect method adds up every loss and subtracts them from 100. The first gives a number; the second tells you where the fuel went.

ByShikhar Singh·Steam Consultant & IT Consultant·Published

You'll learn

  • Run a direct-method efficiency calculation
  • List the losses in an indirect-method test
  • Calculate dry flue gas and moisture losses
  • Know what makes a test trustworthy

Before this: Heat balance and boiler efficiency, Flue gas analysis

BeginnerThe idea in plain words, and where you meet it. No maths.

Two methods

Direct method
η=ms(hg−hf)mf×GCV×100
Symbols in the formula
SymbolMeaningUnit
msSteam generatedkg/h
hg−hfEnthalpy rise, steam minus feedwaterkcal/kg
mfFuel burntkg/h
GCVGross calorific value of the fuelkcal/kg

The indirect method measures the losses instead — flue gas, moisture, unburnt fuel, radiation, blowdown — and computes efficiency as 100 minus their sum. It does not need the steam or fuel flow measured accurately, and it shows which loss to attack.

IntermediateThe formula, its units, and a worked example on real plant numbers.

A direct-method test

Worked example
Direct-method efficiency
Given
  • Over a steady test period: 5,000 kg/h of steam at 10.54 kg/cm²(g), feedwater 80 °C; 950 kg/h of coal at 4,000 kcal/kg GCV.
  1. From steam tables (IF97): hg = 2,781.8 kJ/kg, hf at 80 °C = 335.8 kJ/kg.
  2. Heat to steam: 5,000 × 2,446.0 ÷ 4.1868 = 29,21,066 kcal/h.
  3. Heat in fuel: 950 × 4,000 = 38,00,000 kcal/h.
Answer: Efficiency ≈ 76.9% on GCV.

The direct method is only as good as its measurements. A 3% error in the steam meter or the fuel weighing is a 3% error in efficiency — enough to hide or invent the improvement you are testing.

ExpertThe fine print: where the simple model breaks, and what it costs.

The indirect method, loss by loss

  • Dry flue gas loss — the largest, from stack temperature and excess air.
  • Loss from hydrogen in the fuel, which burns to water and leaves as vapor.
  • Loss from moisture in the fuel and in the combustion air.
  • Loss from carbon monoxide — incomplete combustion.
  • Unburnt carbon in fly ash and bottom ash.
  • Radiation and convection from the boiler casing, and blowdown.
Dry flue gas loss, % of GCV
L1=mcp(Tg−Ta)GCV×100
Symbols in the formula
SymbolMeaningUnit
mDry flue gas per kg of fuelkg/kg
cpSpecific heat of flue gaskcal/kg·°C
Tg−TaStack gas minus ambient air temperature°C
Worked example
Two losses from one test
Given
  • Stack 200 °C, ambient 30 °C; 7.5 kg dry flue gas per kg of coal, cp 0.23; fuel 3% hydrogen and 10% moisture (illustrative composition); GCV 4,000 kcal/kg.
  1. Dry flue gas loss:
    L1=7.5×0.23×1704,000×100=7.3%
  2. Water formed and carried per kg of fuel: 9 × 0.03 + 0.1 = 0.37 kg. Each kilogram takes 584 kcal to evaporate plus 0.45 kcal/kg·°C of superheat to stack temperature.
  3. Moisture and hydrogen loss:
    L2=0.37×(584+0.45×170)4,000×100=6.1%
Answer: 13.4% of the fuel’s heat leaves the stack in these two losses alone. Cutting stack temperature or excess air attacks the first; drier fuel attacks the second.

Key takeaways

  • Direct method: heat to steam ÷ heat in fuel. Simple, but needs accurate steam and fuel measurement.
  • Indirect method: 100 minus the sum of losses. Shows where the fuel goes.
  • Dry flue gas and moisture losses are usually the largest.
  • State the basis, GCV or NCV, with every efficiency figure.

Check your understanding

Questions run from beginner to expert. Try each before opening the answer.

  1. Beginner

    Q1. The indirect method calculates efficiency as:

    1. A.Steam ÷ fuel
    2. B.100 minus the sum of losses
    3. C.Stack temperature ÷ 10
    4. D.GCV ÷ NCV
    Show answer

    B. It adds up the losses.

  2. Intermediate

    Q2. Why is the direct method sensitive to the steam meter?

    1. A.It is not
    2. B.Any error in steam flow is the same error in efficiency
    3. C.Meters read pressure
    4. D.Only for oil
    Show answer

    B. Efficiency is directly proportional to measured steam.

  3. Intermediate

    Q3. Which change reduces dry flue gas loss?

    1. A.Higher stack temperature
    2. B.Lower excess air
    3. C.Wetter fuel
    4. D.More blowdown
    Show answer

    B. Less gas mass per kg of fuel.

  4. Expert

    Q4. Why does hydrogen in the fuel cause a loss?

    1. A.It does not burn
    2. B.It burns to water, which leaves as vapor carrying latent heat
    3. C.It forms ash
    4. D.It raises CO
    Show answer

    B. Each kg of H₂ makes 9 kg of water.

Frequently asked

What is the difference between the direct and indirect method of boiler efficiency?
The direct method divides the heat added to the steam by the heat in the fuel burnt. The indirect method measures each loss — flue gas, moisture, unburnt fuel, radiation, blowdown — and subtracts their total from 100.
Which boiler efficiency method is more accurate?
The indirect method is usually more reliable in the field because it does not depend on accurate steam and fuel flow measurement, and it shows which losses to reduce.

Training a boiler team?

These lessons follow the order we train operators in. We also run on-site operator and maintenance training, built around your own plant.

Boiler operator training →

Sources

  • Bureau of Energy Efficiency, Guide Book 4: Energy Performance Assessment for Equipment and Utility Systems, chapter 1 (Boilers) — Direct and indirect methods and the loss formulas.
  • IS 8753 — Boilers: efficiency testing — Indian standard for boiler efficiency test procedure.