Module 02 · How a Boiler Works5 min read

Boiler Heat Balance and Efficiency: Direct and Indirect Methods

Every kilocalorie a boiler burns goes either into the steam or out as a loss. Accounting for both is the heat balance, and efficiency is the share that reaches the steam. It can be measured from the output side or from the loss side, and each method catches what the other misses.

ByShikhar Singh·Steam Consultant & IT Consultant·Published

You'll learn

  • List where a boiler’s heat goes
  • Calculate efficiency by the direct method
  • Explain the indirect method and why it is more useful for improvement
  • Read a published heat balance

Before this: Enthalpy, Laws of thermodynamics and entropy

BeginnerThe idea in plain words, and where you meet it. No maths.

Where the heat goes

Burn a kilogram of fuel and its heat leaves the boiler by several routes. Most of it should go into the water and steam. The rest is lost: carried up the chimney in hot flue gas, used to evaporate moisture and hydrogen-formed water from the fuel, left as unburnt fuel in the ash, lost as carbon monoxide, and radiated from the hot casing.

Efficiency is the share that reaches the steam. A boiler at 80% efficiency loses one fifth of everything it burns. Because fuel is most of the cost of steam, a few points of efficiency are worth more over a boiler’s life than almost any difference in purchase price.

IntermediateThe formula, its units, and a worked example on real plant numbers.

The direct method

Efficiency, direct method
η=m˙s(hg−hfeed)m˙f×GCV×100
Symbols in the formula
SymbolMeaningUnit
m˙sSteam generatedkg/h
hg−hfeedHeat added per kilogram (convert to kcal if GCV is in kcal)kJ/kg
m˙fFuel burnedkg/h
GCVGross calorific value of the fuelkcal/kg
Worked example
A coal-fired boiler on test
Given
  • 2,000 kg/h of dry saturated steam at 10 kg/cm²(g), feedwater at 80 °C.
  • 400 kg/h of coal with a GCV of 4,000 kcal/kg (an indicative figure; use the lab analysis of your own coal).
  1. Heat to steam: 2,000 × (2,780.1 − 335.8) ÷ 4.1868 = 11,67,618 kcal/h.
  2. Heat in fuel: 400 × 4,000 = 16,00,000 kcal/h.
  3. Efficiency:
    η=11,67,61816,00,000×100=73.0%
Answer: 73.0%. Simple, and it needs only three measurements — but each must be accurate, because an error in any one goes straight into the answer.

The indirect method

Efficiency, indirect method
η=100−(L1+L2+L3+…)

Here each loss is calculated from flue gas analysis, stack temperature, fuel analysis and ash tests, then subtracted from 100. It needs more measurements, but it says why efficiency is what it is, which the direct method cannot.

Heat balance of a coal-fired boiler, GCV basis (BEE worked example)
Loss% of fuel heat
Dry flue gas7.88
Moisture in fuel5.91
Hydrogen in fuel3.44
Carbon lost as CO2.58
Unburnt carbon in bottom ash1.77
Other small losses0.65
Efficiency77.77

Bureau of Energy Efficiency, Guide Book 4, ch. 1, §1.8. Losses total 22.23%.

Two donut charts of where fuel heat goes in a coal-fired and a furnace-oil-fired boiler, from the Bureau of Energy Efficiency worked examples: 77.8% and 84.3% to steam, with dry flue gas the largest loss in both.
Where the fuel’s heat goes, coal against furnace oil. Chart: GyanTosh Fabricators Pvt. Ltd., reusable with credit under CC BY 4.0
ExpertThe fine print: where the simple model breaks, and what it costs.

Reading a heat balance like an auditor

Dry flue gas loss is the largest single loss in both of BEE’s examples, and it is the one an operator controls most directly: it rises with stack temperature and with excess air. Moisture and hydrogen losses are set by the fuel, which is why wet biomass and coal with high inherent moisture can never reach the efficiency of oil or gas, however well the boiler is run.

The basis matters. Indian practice states efficiency on gross calorific value; much European data is on net calorific value, which excludes the latent heat of the water formed from the fuel’s hydrogen. The same boiler reads several points higher on an NCV basis. Two efficiency figures can only be compared on the same basis.

Key takeaways

  • Efficiency is the share of fuel heat that reaches the steam; the rest is losses.
  • Direct method: output ÷ input. Quick, but sensitive to steam metering.
  • Indirect method: 100 − losses. Slower, but shows where to improve.
  • Dry flue gas loss is usually largest; compare efficiencies only on the same GCV/NCV basis.

Check your understanding

Questions run from beginner to expert. Try each before opening the answer.

  1. Beginner

    Q1. A boiler is 80% efficient. What share of the fuel heat is lost?

    1. A.8%
    2. B.20%
    3. C.80%
    4. D.None
    Show answer

    B. 100 − 80 = 20% goes to losses.

  2. Intermediate

    Q2. Which method tells you why a boiler’s efficiency is low?

    1. A.Direct
    2. B.Indirect
    3. C.Both equally
    4. D.Neither
    Show answer

    B. The indirect method quantifies each loss separately.

  3. Intermediate

    Q3. Heat to steam is 10 lakh kcal/h and fuel heat input 12.5 lakh kcal/h. Efficiency?

    1. A.75%
    2. B.80%
    3. C.85%
    4. D.125%
    Show answer

    B. 10 ÷ 12.5 = 0.80.

  4. Expert

    Q4. Why does the same boiler show a higher efficiency on an NCV basis?

    1. A.It burns better
    2. B.NCV excludes the latent heat of water formed from the fuel, so the input is smaller
    3. C.NCV is measured hotter
    4. D.It does not
    Show answer

    B. A smaller denominator gives a larger percentage for the same output.

Frequently asked

What is a boiler heat balance?
An account of where the fuel’s heat goes: the share that reaches the steam and each loss — dry flue gas, moisture and hydrogen in fuel, unburnt carbon, CO, radiation. The losses and the useful heat add up to 100%.
What is the difference between the direct and indirect methods?
The direct method divides heat in steam by heat in fuel. The indirect method calculates each loss and subtracts their total from 100%, which shows where efficiency is being lost.
What is a good boiler efficiency?
It depends on the fuel. BEE’s worked examples show about 78% for a coal-fired boiler and 84% for furnace oil on a GCV basis; wet biomass is usually lower because of moisture losses.

Related equipment

Training a boiler team?

These lessons follow the order we train operators in. We also run on-site operator and maintenance training, built around your own plant.

Boiler operator training →

Sources

About the author

Shikhar SinghSteam Consultant & IT Consultant

Shikhar Singh is a Steam Consultant and IT Consultant at GyanTosh Fabricators Pvt. Ltd., where he works on steam system sizing, condensate recovery and the engineering content published on this site.

Full profile and background →