Economizers and Air Preheaters: Recovering Heat From Flue Gas

Flue gas leaving the boiler is still hot, and that heat is the largest loss in most boilers. An economizer uses it to warm the feedwater; an air preheater uses it to warm the combustion air. Both put heat back into the boiler that would otherwise go up the chimney.

ByShikhar Singh·Steam Consultant & IT Consultant·Published

You'll learn

  • Explain where economizers and air preheaters sit and what they heat
  • Calculate the heat an economizer recovers and the fuel it saves
  • Use the sourced rules of thumb for flue gas, feedwater and air temperatures
  • Know the corrosion limit on how far flue gas can be cooled

Before this: Heat balance and boiler efficiency, Sensible heat

BeginnerThe idea in plain words, and where you meet it. No maths.

Catching the heat before it leaves

Gas leaves the last boiler tubes well above the steam temperature, because heat only flows from hot to cold and the water inside is at saturation temperature. An economizer is a bank of finned or plain tubes in the flue duct after the boiler, through which the feedwater passes on its way in. The gas warms the water, the water enters the boiler hotter, and the boiler burns less fuel to make the same steam.

An air preheater does the same job for the combustion air: it takes heat from the outgoing gas and gives it to the incoming air. Hotter air also helps difficult fuels such as wet biomass and low-grade coal ignite and burn out.

IntermediateThe formula, its units, and a worked example on real plant numbers.

How much an economizer saves

Worked example
An economizer on a 2 TPH boiler
Given
  • 2,000 kg/h of feedwater at 10 kg/cm²(g), warmed from 80 °C to 110 °C.
  1. Water enthalpy rises from 335.8 to 462.0 kJ/kg.
  2. Heat recovered:
    2,000×(462.0−335.8)=2,52,549 kJ/h=70 kW
  3. As a share of the heat needed per kilogram of steam:
    126.32,780.1−335.8=5.2%
Answer: About 5.2% of the boiler’s heat now comes from flue gas that was being thrown away — a fuel saving of roughly that size.
What one percentage point of efficiency takes, as published
ChangeWorth about 1%Source
Cooler flue gas22 °CUNEP; US DOE says 40 °F (22 °C)
Hotter feedwater6 °CUNEP
Hotter combustion air20 °CUNEP

UNEP, Energy Efficiency Guide for Industry in Asia (Boilers, §6.3); US DOE Steam Tip Sheet #3.

The rules agree with the arithmetic above. A 5.2% saving implies the flue gas leaves roughly 114 °C cooler, which is the kind of drop a well-sized economizer delivers.

ExpertThe fine print: where the simple model breaks, and what it costs.

The acid dew point, and what limits recovery

Flue gas from fuels containing sulfur carries sulfur trioxide, which combines with water vapor to form sulfuric acid at a temperature well above the ordinary water dew point. If any metal surface in the gas path is colder than that acid dew point, acid condenses on it and corrodes it quickly. In an economizer the coldest metal is at the feedwater inlet, so it is the feedwater inlet temperature, not the gas temperature, that has to be kept above the limit.

That is why economizers on oil- and coal-fired boilers are designed with a minimum feedwater inlet temperature and a minimum gas exit temperature, and why a deaerator upstream helps twice: it removes oxygen and it raises the feedwater temperature. Clean fuels like natural gas allow much colder exit gas, and condensing economizers deliberately cool below the water dew point to recover latent heat too, with corrosion-resistant materials.

Two other limits are mechanical. An economizer is a pressure part on the feedwater line, so it must handle full feed pump pressure and must not steam: if water boils inside it at low load, it can hammer and lose flow. And on solid fuels, ash fouls economizer and air preheater surfaces, so soot blowing and access for cleaning decide how much of the design saving is kept in service.

Key takeaways

  • Economizers heat feedwater, air preheaters heat combustion air, both from outgoing flue gas.
  • Raising feedwater from 80 to 110 °C at 10 kg/cm²(g) saves about 5% of fuel.
  • Published rules: 22 °C cooler flue gas, 6 °C hotter feedwater or 20 °C hotter air ≈ 1% efficiency.
  • Keep metal above the acid dew point on sulfur-bearing fuels; on economizers that means feedwater inlet temperature.

Check your understanding

Questions run from beginner to expert. Try each before opening the answer.

  1. Beginner

    Q1. What does an economizer heat?

    1. A.Combustion air
    2. B.Feedwater
    3. C.Fuel
    4. D.Steam
    Show answer

    B. It warms feedwater with flue gas heat before the water enters the boiler.

  2. Intermediate

    Q2. By the published rule, cooling flue gas by 44 °C is worth about how much efficiency?

    1. A.0.5%
    2. B.1%
    3. C.2%
    4. D.4%
    Show answer

    C. About 22 °C per point, so 44 °C ≈ 2%.

  3. Intermediate

    Q3. Which raises efficiency by about 1% according to UNEP?

    1. A.6 °C hotter feedwater
    2. B.6 °C hotter flue gas
    3. C.1% more excess air
    4. D.A taller chimney
    Show answer

    A. UNEP gives 6 °C of feedwater temperature per point.

  4. Expert

    Q4. On a coal-fired boiler, which temperature must be kept above the acid dew point to protect the economizer?

    1. A.Steam temperature
    2. B.Feedwater inlet temperature, since it sets the coldest metal
    3. C.Ambient air
    4. D.Drum temperature
    Show answer

    B. The coldest economizer metal is at the water inlet.

Frequently asked

How much fuel does a boiler economizer save?
Typically a few percent. As a rule, each 6 °C rise in feedwater temperature saves about 1% of fuel; warming feedwater from 80 to 110 °C at 10 kg/cm²(g) saves about 5.2%.
What is the difference between an economizer and an air preheater?
Both recover heat from flue gas. An economizer heats the boiler feedwater; an air preheater heats the combustion air.
Why can’t flue gas be cooled as far as possible?
With sulfur-bearing fuels, cooling metal below the acid dew point condenses sulfuric acid and corrodes it. Clean gas allows deeper cooling.

Training a boiler team?

These lessons follow the order we train operators in. We also run on-site operator and maintenance training, built around your own plant.

Boiler operator training →

Sources

About the author

Shikhar SinghSteam Consultant & IT Consultant

Shikhar Singh is a Steam Consultant and IT Consultant at GyanTosh Fabricators Pvt. Ltd., where he works on steam system sizing, condensate recovery and the engineering content published on this site.

Full profile and background →