Measuring Conductivity (TDS) and Flue Gas Oxygen

Two measurements let a boiler control its own losses. A conductivity probe in the boiler water lets blowdown follow TDS exactly. An oxygen analyzer in the flue lets the burner trim its air continuously. Both pay for themselves in fuel.

ByShikhar Singh·Steam Consultant & IT Consultant·Published

You'll learn

  • Explain how conductivity measures TDS
  • Describe automatic TDS blowdown control
  • Describe in-situ oxygen analyzers and O₂ trim
  • Maintain both so they stay accurate

Before this: TDS control and blowdown, Flue gas analysis

BeginnerThe idea in plain words, and where you meet it. No maths.

Two automatic savings

Blowdown done by hand is usually too much or too little, because the attendant cannot see TDS between tests. A conductivity probe can: it reads continuously and opens the blowdown valve only when TDS reaches its set point.

Burner air set once at commissioning drifts with fuel quality, air temperature and wear. An oxygen analyzer in the flue sees the drift and lets the control system correct the air continuously, keeping excess air near its best value.

IntermediateThe formula, its units, and a worked example on real plant numbers.

How they work

  • Conductivity: dissolved salts let water conduct electricity, and conductivity rises with their concentration. A probe in the boiler measures it; a controller compensates for temperature and converts to an approximate TDS.
  • Automatic TDS control: when conductivity reaches the set point, a blowdown valve opens until it falls back, holding TDS just under the limit.
  • Zirconia oxygen analyzer: a heated zirconia cell in the flue duct produces a signal related to the oxygen difference between flue gas and a reference air.
  • O₂ trim: the measured oxygen adjusts the burner’s air damper or fan speed around its basic fuel–air curve.
ExpertThe fine print: where the simple model breaks, and what it costs.

Keeping them honest

  • Conductivity probes foul and scale; clean them and check their reading against a sample tested by hand.
  • Temperature compensation must be right: conductivity changes strongly with temperature.
  • Oxygen analyzers drift; check them against calibration gases on schedule.
  • Mount the oxygen probe where the gas is representative and where air leaks cannot dilute it, or the trim will chase a false reading.
  • Trim limits: O₂ trim adjusts around a safe fuel–air curve within limits, so a failed analyzer cannot drive the burner rich.

Key takeaways

  • Conductivity measures TDS continuously; automatic control opens blowdown only when needed.
  • Zirconia analyzers measure flue O₂; O₂ trim corrects burner air continuously.
  • Both need cleaning, calibration and representative mounting.
  • Trim acts within safe limits around a fixed fuel–air curve.

Check your understanding

Questions run from beginner to expert. Try each before opening the answer.

  1. Beginner

    Q1. What does automatic TDS control do?

    1. A.Adds chemicals
    2. B.Opens blowdown only when boiler water TDS reaches its set point
    3. C.Raises pressure
    4. D.Measures oxygen
    Show answer

    B. It holds TDS just under the limit.

  2. Intermediate

    Q2. What sensor is usually used for flue gas oxygen?

    1. A.Thermocouple
    2. B.Zirconia cell
    3. C.Bourdon tube
    4. D.Float
    Show answer

    B. Heated zirconia measures oxygen difference.

  3. Intermediate

    Q3. Why must conductivity readings be temperature-compensated?

    1. A.Conductivity changes strongly with temperature
    2. B.For display
    3. C.Regulation
    4. D.They need not be
    Show answer

    A. Hot water conducts much better than cold at the same TDS.

  4. Expert

    Q4. Why does O₂ trim act only within limits?

    1. A.To save power
    2. B.So a failed analyzer cannot drive the burner unsafely rich
    3. C.Regulation of color
    4. D.No reason
    Show answer

    B. The basic fuel–air curve remains the safety backbone.

Frequently asked

How does automatic boiler blowdown control work?
A conductivity probe measures boiler water TDS continuously; when it reaches the set point, the controller opens a blowdown valve until TDS falls back, so the boiler blows down only as much as needed.
What is O2 trim on a boiler?
Continuous adjustment of combustion air using a flue gas oxygen analyzer, keeping excess air near its best value as fuel and conditions change.

Training a boiler team?

These lessons follow the order we train operators in. We also run on-site operator and maintenance training, built around your own plant.

Boiler operator training →

Sources

  • Bureau of Energy Efficiency, Guide Book 2: Energy Efficiency in Thermal Utilities, chapter 2 (Boilers) — Blowdown control and combustion control for efficiency.

About the author

Shikhar SinghSteam Consultant & IT Consultant

Shikhar Singh is a Steam Consultant and IT Consultant at GyanTosh Fabricators Pvt. Ltd., where he works on steam system sizing, condensate recovery and the engineering content published on this site.

Full profile and background →