Module 10 · Measurement3 min read

Measuring Pressure and Temperature in a Boiler Plant

Pressure and temperature are the two numbers that run a boiler plant. Local gauges let an attendant see them; transmitters send them to controls and records. Each instrument has a range where it is accurate and ways it goes wrong.

ByShikhar Singh·Steam Consultant & IT Consultant·Published

You'll learn

  • Describe the common pressure and temperature instruments
  • Choose between a gauge and a transmitter
  • Understand thermowells and sensor types
  • Know why accuracy and calibration matter

Before this: Gauge vs absolute pressure, Water level and pressure gauges

BeginnerThe idea in plain words, and where you meet it. No maths.

Local gauges and transmitters

A local pressure gauge with a Bourdon tube shows pressure on a dial; a bimetal or liquid-in-glass thermometer shows temperature. They need no power and are what an attendant reads on rounds.

A transmitter measures the same quantity electronically and sends a signal, usually 4–20 mA or a digital protocol, to the control system, the display panel and the data logger. Controls, alarms and trips act on transmitters, not on dials.

IntermediateThe formula, its units, and a worked example on real plant numbers.

Temperature sensors

Common temperature sensors
SensorRange and characterTypical use
Bimetal dial thermometerLocal reading, modest accuracyFeed tank, pipework, local checks
RTD (Pt100)Accurate, stable, up to several hundred °CFeedwater, steam, process control
ThermocoupleWide range, very high temperaturesFlue gas, furnace, superheater

Sensors in pressurized lines sit in thermowells: closed tubes welded or screwed into the pipe, so the sensor can be removed without opening the line. A thermowell slows response a little and must be strong enough for the flow and pressure.

ExpertThe fine print: where the simple model breaks, and what it costs.

Accuracy, range and calibration

Instruments are most accurate in the middle of their range. A pressure gauge should normally read in the middle third of its scale at working pressure: one that sits near the top is stressed and near its limit; one that sits near the bottom gives poor resolution.

Error in pressure becomes error in temperature for saturated steam. Near 1 kg/cm²(g), saturation temperature changes by about 15.8 °C per kg/cm², so a gauge reading 0.2 kg/cm² wrong misstates steam temperature by about 3.2 °C — significant for a process held to a few degrees.

  • Calibrate transmitters and test gauges against reference instruments at set intervals and after any overrange.
  • Protect pressure instruments from steam with siphons and from pulsation with snubbers.
  • Put thermocouples where the gas is representative: not in a corner of a duct where it stratifies.
  • Record calibrations; an uncalibrated trip instrument is an untested trip.

Key takeaways

  • Local gauges for rounds; transmitters for controls, alarms and records.
  • Bimetal for local temperature; RTDs for accuracy; thermocouples for high temperatures.
  • Read gauges in the middle third of their scale; protect them with siphons and snubbers.
  • For saturated steam, pressure error is temperature error; calibrate regularly.

Check your understanding

Questions run from beginner to expert. Try each before opening the answer.

  1. Beginner

    Q1. What do boiler controls and trips act on?

    1. A.Local dial gauges
    2. B.Transmitter signals
    3. C.The attendant’s log
    4. D.Nothing
    Show answer

    B. Transmitters send signals that controls use.

  2. Intermediate

    Q2. Which sensor suits flue gas and furnace temperatures?

    1. A.Liquid-in-glass
    2. B.Thermocouple
    3. C.Bimetal dial only
    4. D.Pressure gauge
    Show answer

    B. Thermocouples cover very high temperatures.

  3. Intermediate

    Q3. What is a thermowell for?

    1. A.Heating the sensor
    2. B.Letting the sensor be removed without opening the line
    3. C.Measuring pressure
    4. D.Reducing flow
    Show answer

    B. It is a pressure-tight pocket for the sensor.

  4. Expert

    Q4. Where on its scale should a pressure gauge normally read at working pressure?

    1. A.Near zero
    2. B.Middle third
    3. C.At full scale
    4. D.Off scale
    Show answer

    B. Best accuracy and least stress.

Frequently asked

What is the difference between an RTD and a thermocouple?
An RTD measures temperature by the change in a metal’s resistance and is accurate and stable to a few hundred °C. A thermocouple measures the voltage between two dissimilar metals and covers much higher temperatures with less accuracy.
Why should a pressure gauge read in the middle of its scale?
Gauges are most accurate and least stressed in the middle third of their range; near full scale they wear and lose accuracy.

Related equipment

Training a boiler team?

These lessons follow the order we train operators in. We also run on-site operator and maintenance training, built around your own plant.

Boiler operator training →

About the author

Shikhar SinghSteam Consultant & IT Consultant

Shikhar Singh is a Steam Consultant and IT Consultant at GyanTosh Fabricators Pvt. Ltd., where he works on steam system sizing, condensate recovery and the engineering content published on this site.

Full profile and background →